What is possible – and how do you get started?
As industry becomes increasingly digitalised, the demand for communication and data sharing has risen significantly. Where heat processes were previously controlled using analogue signals, there is now a growing need to integrate power controllers directly into the network. This provides far better control, more documentation, and easier troubleshooting.
One of the most widely used standards today is Profinet, which makes it possible to connect power controllers directly to PLC and SCADA systems. For machine builders, this means that heating elements and process heating are no longer a “black box”, but an integrated part of the entire production line.
From analogue signals to network integration
Traditionally, power controllers have been controlled via analogue signals – typically 0–10 V or 4–20 mA. This still works well in many installations, but has clear limitations: only one signal at a time and no direct diagnostics.
With Profinet, control becomes far more flexible. Here, the controller can both send and receive a wide range of signals – from setpoints to measurements and alarm status. This means you are no longer dependent on additional measuring instruments or manual checks. Data is available live in the PLC and can be displayed on SCADA screens or logged for later use.
What can you gain from Profinet in a power controller?
When a power controller such as the Eurotherm EPack or EPower is connected to Profinet, it opens up a range of possibilities:
- Setpoints via the network
– Instead of sending an analogue signal, the PLC can send reference values digitally. This provides high precision and eliminates the risk of noise on analogue cables. - Live measurements
– Current, voltage, power, and status can be read directly. This provides better insight into how the heating element is operating and makes it possible to monitor the load in real time. - Alarm status
– Alarms such as “missing load”, undervoltage, or phase imbalance can be read directly in the PLC. This means faster troubleshooting and fewer unplanned stoppages. - Load diagnostics
– The controller can monitor the heating element’s impedance. If an element is disconnected, you can see it immediately in the system. This provides an extra level of operational safety. - Communication data
– Profinet also provides access to system alarms such as “loss of communication”. Here you can configure how the controller should respond, e.g. by switching to a safe state.
When communication fails
A key aspect of network integration is handling communication faults. If the Profinet connection drops out, the power controller will typically continue at the latest setpoint. In some processes this may be acceptable, but in others it can be critical.
Therefore, it is recommended to configure a fallback strategy. For example, the controller can be set to shut down if the network disappears, or switch to an analogue backup signal. Many machine builders choose a hybrid solution where an analogue signal is still connected as an additional safety measure.
Hardwired signals as a safety layer
Although Profinet opens up a wide range of possibilities, we always recommend hardwiring the most critical signals. This applies in particular to:
- Enable
- Setpoint (analogue reference)
- Alarm signal
The reason is simple: these signals must be available regardless of how the network behaves. Profinet is ideal for monitoring, data collection, and advanced control, but to ensure maximum operational reliability, the vital functions should still be connected directly.
This combination provides the best of both worlds: the robust safety of hardwired signals and the flexibility of digital communication via Profinet.
Benefits in day-to-day operation
Profinet integration is not only about better control – it is also about making everyday work easier for technicians and operators:
- Faster troubleshooting: When alarms and measurements can be viewed directly in the PLC/SCADA, time is saved on fault-finding in the control cabinet.
- Less downtime: Issues are detected before they develop into actual stoppages.
- Better documentation: All data can be logged and used for quality assurance, audits, or process optimisation.
- Future-proofing: Network-based communication is a natural part of Industry 4.0 and provides better integration into future systems.
Experience from industry
Several of our customers have already implemented Profinet in their plants – successfully. They particularly highlight the value of live data and alarm handling, which makes it easier to keep production stable. At the same time, the integration enables better collaboration between process engineers and automation specialists, because everyone works with the same data in real time.
How to get started
Getting started with Profinet does not require a complete rebuild of the plant. On the contrary, it can often be implemented step by step:
- Start with one power controller – and test the integration in a plant where the operational risk is low.
- Use iTools for configuration – this is where the signals to be read and written via Profinet are defined.
- Test fallback scenarios – what happens if communication is lost? Ensure that the plant goes into a safe state.
- Scale gradually – once the integration works in one plant, the same setup can be transferred to multiple controllers.
Profinet integration in power controllers opens up a new way of working with process heating. With live data, alarms, and diagnostics, you gain far greater transparency – and more stable operation. At the same time, maintenance and troubleshooting become easier, and processes can be documented better.
For machine builders and the process industry, it is a logical step towards more intelligent and future-proof plants.