Article content
It is rarely discovered during commissioning – but in day-to-day operation, when the load is constant.
In practice, the problems are often caused by excessive watt density, incorrect airflow, or inadequate temperature control. The system may work at start-up, but over time service life is reduced, safety devices trip, and operation becomes unstable.
This article reviews what actually matters when heating elements for air are to be designed – and which mistakes most often lead to operational issues.
How to design an efficient heating element for air heating
Heating air places specific requirements on the design and sizing of heating elements.
Unlike liquids, which conduct heat efficiently, air has low thermal conductivity and therefore requires a balanced combination of watt density, airflow, and temperature control. Incorrect design can lead to overheating, uneven heat distribution, and reduced service life of the element.
Air properties place requirements on the heating element
Air has a relatively low heat capacity and poor thermal conductivity.
This means that heat is only removed efficiently from the heating element surface if there is sufficient air movement – either through natural or forced convection (fan or duct flow).
With natural convection, the surface temperature can quickly become very high because the warm air rises away from the element but is not replaced quickly enough. Therefore, the watt density should be kept low (2–5 W/cm²).
With forced convection, where the airflow moves quickly across the element, a higher load can be allowed (5–10 W/cm²) depending on the air velocity and temperature.
Temperature and material selection
The temperature range is decisive for the choice of both sheath and insulation material.
At low to moderate temperatures (up to approx. 400 °C), stainless steel grades such as AISI 304 can be used.
At higher temperatures (400–800 °C), AISI 316L or Incoloy 800/825 is recommended, as they offer better oxidation and heat resistance.
If the air temperature exceeds approx. 600 °C, attention should be paid to incandescence and burn-off of particles in the air, which can damage both the heating element and the process. Correct control and material selection are critical here.
Airflow and heat distribution
Airflow directly affects the heating element surface temperature.
As a rule of thumb, for each doubling of air velocity, watt density can be increased by 30–50% because heat is removed more efficiently.
Uneven flow – e.g., in duct corners or around flanges – can create local hot spots.
This should be avoided through correct positioning, flow straightening, and possibly baffles, so that the air passes evenly over all elements.
Uniform air distribution and avoidance of air pockets
One of the most common problems in air heating systems is uneven airflow over the heating element.
In duct heaters or air heaters, blockages, turbulence, or dead zones can mean that certain parts of the element do not receive sufficient airflow.
When the airflow is locally low or completely stagnant, the heating element cannot dissipate heat effectively – and the temperature in these areas rises quickly.
The result is often:
- Overheating and damage to the heating element.
- Degradation of the insulation material (magnesium oxide).
- Activation of safety thermostats and downtime.
To avoid this, ensure:
- Uniform air distribution across the entire surface of the heating element.
- Use of flow control or air distribution plates (baffles) at duct inlets.
- Avoid turbulent corners and ducts that are too narrow, where the air is slowed down.
- Verification measurement of airflow (m/s) during the design phase to confirm uniform distribution.
A correctly designed airflow not only extends the service life of the heating element, but also ensures a stable temperature profile and energy-efficient operation throughout the system.
Temperature control and safety
A heating element for air should always be designed with suitable temperature sensors and safety thermostats.
Typically used:
- PT100 or thermocouple sensor for control.
- Safety thermostat (manual reset) as protection against overtemperature.
In addition, the heating element should only be activated once airflow has been established – to avoid overheating during start-up. This can be ensured with a flow switch or pressure sensor.
Typical design parameters for air heating elements
| Parameter | Natural convection | Forced convection |
| Watt density | 2-5 W/cm² | 5-10 W/cm² |
| Air temperature | 50-300 °C | 50-600 °C |
| Typical materials | AISI 304 / 316 | AISI 316 / Incoloy 800 |
| Applications | Cabin heating, cabinets, and drying cabinets | Process air, ventilation ducts, and ovens |
Get advice on air heating elements for your application
An efficient heating element for air heating requires the right balance between temperature, airflow, and material selection. When air distribution is uniform and the watt density is correctly sized, you achieve not only high efficiency, but also longer service life and more stable operation. The better the heating element is adapted to the movement of the air, the more energy-efficient the overall installation becomes.
At Newtronic, we are ready to help you all the way. With many years of experience in the design and sizing of air heating elements for industrial and technical purposes, we advise on the optimal combination of power, airflow, temperature control, and watt density – always based on your specific application.
Please contact us for a non-binding discussion about your solution.
Call +45 7669 7090, or email info@newtronic.dk – and together we will find the solution that provides you with the best and most reliable air heating.