How to optimise freeze protection for pipes

Pipe freeze protection: Avoid hidden energy drains in your plant

In many industrial plants, freeze protection systems run far more than is actually necessary. The result is unnecessarily high power consumption, unnecessary operating hours on heating cables, and higher operating costs.

The problem is often that the control is not adapted to the actual heat loss, but instead operates to a set threshold value—regardless of whether heat is actually needed or not.

In this article, we review the results of an extensive test of three different control methods for pipe freeze protection. The test clearly shows how significant savings can be achieved by choosing a control system that responds to the actual conditions on the pipe rather than simply to the outdoor temperature.

The challenge with conventional ambient control

One of the most widely used solutions on the market is the mechanical ambient thermostat. It measures the outdoor temperature and switches the heating cables fully on when the temperature drops below a set value—typically around 5 °C. When the temperature rises above the threshold again, it switches off.

The problem is that this method does not take into account the actual heat loss from the pipe. In practice, this means that the heating system is often on for 2,000–3,500 hours a year, even though the real need is typically only 400–700 hours. The result is wasted energy, higher CO₂ emissions, and unnecessary wear on the system.

Test set-up – three control methods under the same conditions

To identify the most energy-efficient solution, Thermon carried out a winter/spring test in which three different control types were compared under identical conditions:

  1. Ambient sensor (mechanical thermostat) – measures the outdoor temperature.
  2. Mechanical pipe sensor – mechanically measures the pipe temperature directly on the pipe.
  3. Electronic pipe sensor (ECM) – electronically measures the pipe temperature with high precision and regulates output according to the actual heat loss.

The test was conducted on identical 4” steel pipes, insulated with 50 mm mineral wool, and with the same type of heating cable. All measurements were carried out using certified equipment and documented in a monitoring system.

Would you like to read more about the test?

Results – major differences in energy consumption

The test results showed significant differences in energy consumption:

Control typeEnergy consumption (% of ambient)Typical operating time per year AdvantagesDisadvantages
Ambient sensor (mechanical thermostat)100 %2,000–3,500 hoursLow purchase cost, simple technology.High energy consumption, unnecessary operating hours.
Mechanical pipe sensor56 %800–1,200 hoursBetter than ambient, more accurate control.Less accurate than electronic control.
Electronic pipe sensor (ECM)19 %400–700 hoursMaximum energy efficiency, precise regulation, lower operating costs, longer service life.Higher purchase cost

Compared with ambient control, the mechanical pipe sensor reduces energy consumption by approx. 44%, while electronic ECM control provides savings of as much as 81%.

How ECM works – precision in practice

The electronic ECM control is equipped with a Pt100 temperature sensor, which continuously measures the pipe temperature. The control then adjusts the output so that it only compensates for the current heat loss.

This means the system always delivers the required amount of heat—neither more nor less.
The benefits of this are:

  • Significantly lower energy consumption – up to 81% savings compared with ambient control.
  • Lower CO₂ emissions – important in relation to ESG and sustainability strategies.
  • Reduced wear – fewer operating hours extend the service life of both heating cables and components.
  • Lower maintenance – fewer components and fewer start/stop cycles.

Financial perspective – fast payback

Although the ECM solution requires a higher investment than both ambient and a mechanical pipe sensor, calculations show that the payback time can be very short.

Example (fictitious, based on typical conditions):
Plant: 20 heating circuits of 1 kW each

Operating time/year:

  • Ambient: 2,500 hours
  • ECM: 500 hours

Annual consumption:

  • Ambient: 50,000 kWh
  • ECM: 10,000 kWh

Annual savings: 40,000 kWh

ESG and sustainability – more than just economics

With increasing requirements for CO₂ reduction—both legislatively and from customers—energy efficiency is playing an ever-greater role in industry.

By reducing electricity consumption by up to 81%, companies can both improve their climate footprint and strengthen their ESG profile.

In addition, the savings can be documented and actively used in CSR reports and dialogue with stakeholders.

Technical perspective – why precision means everything

In freeze protection, it is not only a question of delivering heat, but of delivering the right amount of heat at the right time.

An ambient thermostat is essentially blind to what is happening on the pipe itself and therefore cannot optimise for heat loss.

The mechanical pipe sensor is a step in the right direction, but lacks the precision and adaptability that an electronic control system offers.

With ECM, you get a solution that continuously balances need and consumption—a technology that is particularly relevant as energy prices and sustainability requirements increase.

The future standard for freeze protection

Thermon’s test clearly shows that electronic pipe-sensor control (ECM) is the most energy-efficient method for pipe freeze protection.

For companies, this means not only lower electricity bills, but also a stronger position in relation to ESG, sustainability, and future environmental requirements.

Are you considering upgrading your freeze protection system? Contact us for a review of your plant and an estimate of how much you can save—both in DKK, kWh and CO₂.