Heating cable for
freeze protection and temperature maintenance
A self-regulating heating cable is used for freeze protection and temperature maintenance on pipes, tanks, valves and technical equipment in industrial plants.
The heating cable adjusts its output to the temperature around the cable, making the solution suitable for installations with varying temperature conditions. At Newtronic, we assist with selection, sizing, control and documentation, ensuring that the self-regulating heating cable matches the specific application, installation and operating conditions.
When frost and heat loss can affect operations
Self-regulating heating cable is used in industrial plants where pipes, valves, tanks, flanges or technical equipment must be protected against frost. For many companies, freeze protection is the primary reason for choosing heat tracing, because frost damage can quickly lead to burst pipes, stopped flow, leaks and unplanned downtime.
The cable adjusts its heat output to the temperature around the installation. When the temperature drops, output increases. When the temperature rises, output is reduced. This makes self-regulating heating cables suitable for installations where temperature conditions vary along the pipe run, or where parts of the plant are more exposed than others.
Temperature maintenance in critical processes
Self-regulating heating cables are not only used for freeze protection. In many process plants, temperature maintenance is crucial to ensure that the medium retains the right properties throughout the process.
This applies, for example, to sugar-containing liquids, syrup, fats, oil, chemical media and other products that can crystallise, become too viscous or create deposits if the temperature drops. Here, heat tracing is not only about keeping the installation frost-free, but about ensuring stable flow, consistent process quality and fewer operational issues.
In these applications, the self-regulating heating cable must be sized based on the medium’s properties, the desired maintenance temperature, pipe size, insulation, ambient temperature and control requirements. A correctly designed solution reduces the risk of blockages, uneven temperature and unnecessary manual cleaning or service.
Correct sizing starts with the application
Although self-regulating heating cables are flexible in use, the solution must still be selected and sized correctly. A cable for simple freeze protection does not necessarily have the same requirements as a cable for temperature maintenance in a process line.
At Newtronic, we start from the installation’s function and operating conditions. Among other things, we look at the lowest ambient temperature, desired temperature, pipe material, insulation thickness, voltage level, installation conditions and any documentation requirements. This way, the cable is selected as part of a complete heat tracing solution—not as a standalone standard component.
Cable, accessories and control must work together
A self-regulating heating cable performs best when the cable, accessories, insulation and control are considered together from the outset. Power connection kits, end seals, splices, sensors, thermostats and control panels all affect installation, operation and service.
For smaller plants, simple thermostat control is often sufficient. For larger or more critical installations, there may be a need for temperature sensors, monitoring, alarms and central control of multiple heating circuits. This gives operations staff a better overview and makes it easier to detect faults before they develop into downtime.
Self-regulating heating cables for demanding environments
Industrial heating cables are often installed in environments with moisture, cold, chemical exposure, outdoor placement or special safety requirements. Therefore, both the cable type, outer jacket, installation method and documentation must be selected for the specific installation.
In EX areas, the entire solution must be assessed as a whole. It is not enough to choose a cable that suits the area. Temperature limitation, control, accessories, installation, insulation and documentation must also be aligned with the zone classification, temperature class and the plant’s other requirements.
Heating cables from Thermon
Newtronic supplies self-regulating heating cables and accessories from Thermon, one of the leading manufacturers in heat tracing. This provides access to proven cable systems for both freeze protection, temperature maintenance and more demanding industrial applications.
We advise on selecting cable type, output, control and accessories, ensuring the solution fits both the installation and subsequent operation.
Get advice on self-regulating heating cable
Do you need a self-regulating heating cable for freeze protection or temperature maintenance? Contact Newtronic for advice and project engineering. We help clarify the need, size the solution and ensure that cable, accessories, control and documentation match the plant’s requirements.
Products you may also be interested in
FAQ
BSX is typically used for freeze protection and general temperature maintenance up to 65°C and is available in several power outputs. RSX is also designed for temperatures up to 65°C, but delivers a higher output of approx. 49 W/m at 10°C and is therefore relevant where heat loss is greater. HTSX is developed for more demanding process applications and can be used for temperature maintenance up to 150°C, as well as withstand short-term temperature exposure up to 250°C. The correct cable is therefore selected based on temperature, heat loss and process conditions.
The output in W/m is stated at a specific reference temperature, typically 10°C. A self-regulating heating cable does not deliver the same output all the time. When the pipe gets colder, the cable increases its heat output, and when the temperature rises, the output is reduced. Therefore, you should look at the cable’s output curve—not just the W/m figure—when sizing the solution.
Yes. Self-regulating heating cables have a parallel circuit design and can be cut to the required length within the cable type’s permitted circuit lengths. This makes installation flexible and reduces the need for factory-made cables in fixed lengths. After adjustment, the cable must be terminated with the correct power connection and end kits.
Self-regulating heating cables offer the advantage that output is reduced locally as the temperature rises. This means that certain types of self-regulating cable can be overlapped without the same risk of localised overheating as with traditional resistance cables. However, installation must always be carried out in accordance with the installation instructions for the specific cable type.
Yes. Self-regulating does not mean that the heating cable automatically switches off completely. The cable’s heat output—and therefore its power consumption—decreases as the temperature rises and increases again as the temperature falls. If the system must switch off completely at a specific temperature or be controlled more precisely, the heating cable can be combined with a thermostat or other temperature control.